Gas/liquid boiler ENP | Thermostahl România

Fuels

Liquid/gases

ENP - Gas/liquid fuel boiler
35 - 4.000 kW

ENERSAVE is a highly efficient pressurized steel boiler for function on gas or liquid fuels. The function is based on reversed flame in the fire chamber. All surfaces coming in contact with fire are cooled by water.

Its construction is cylindrical, with large fire chamber, improved heat exchanger surfaces and high performance turbinators. It is of high back- pressure in the fire chamber, designed to function with pressurized liquid or gas burners (the burner is not included).

The boiler has a robust construction which is ensured with quality control at every production step. Nominal working pressure is 6 bar. For models ENP 120-700kW, modular construction of the boiler is available on request.

Suitable control panel for one or two-stage burners. Tested and CE marked according to the European Standard for boilers EN 303-3.

High quality materials
Heating pump control
Control panel for one/two stage burner
3 years warranty
Safety thermostat
ENP - Gas/liquid fuel boiler
35 - 3.000 kW

Fuels

Liquid/gases

ENERSAVE is a highly efficient pressurized steel boiler for function on gas or liquid fuels. The function is based on reversed flame in the fire chamber. All surfaces coming in contact with fire are cooled by water.

Its construction is cylindrical, with large fire chamber, improved heat exchanger surfaces and high performance turbinators. It is of high back- pressure in the fire chamber, designed to function with pressurized liquid or gas burners (the burner is not included).

The boiler has a robust construction which is ensured with quality control at every production step. Nominal working pressure is 6 bar. For models ENP 120-700kW, modular construction of the boiler is available on request.

Suitable control panel for one or two-stage burners. Tested and CE marked according to the European Standard for boilers EN 303-3.

High quality materials
Heating pump control
Control panel for one/two stage burner
3 years warranty
Safety thermostat
MAIN FEATURES

Round-shaped fire chamber with large heat exchange surface

Robust construction, without elements

High efficiency, up to 93%

Comply to requirements of the latest European Energy Efficiency Directive

Tubed heat exchanger with stainless steel turbinators

Cooled-bottom construction

Control panel equipped with safety thermostat. Provides thermostatic control of the burner and pump

Compatible with all burners of European origin

Working pressure 6 bar

High quality materials and compenents

WORKING PRINCIPLE

ENP hot water boilers have high back-pressure in the fire chamber, designed to function with pressurized liquid or gas burners.

The function is based on reversed flame in the fire chamber, with three passes of the exhaust gases. All surfaces coming in contact with fire are water cooled. Most of the heat is transferred to water through radiation. The first two passes are in the fire chamber, then the exhaust gases are guided to the peripheral smoke tubes, in which the third pass is realized. Special turbinators are positioned inside the smoke tubes to increase boiler’s efficiency.

After passing the smoke tubes the exhaust gases are guided to the smoke box and then to the chimney.

BOILER CONSTRUCTION

BOILER CONSTRUCTION

1. Control panel

2. Boiler door

3. Burner mounting flange

4. Fire chamber

5. Boiler return

6. Chimney diameter

7. Boiler return

CONTROLER EN-2S
 

Control panel functions:

heating pump

buner (one or two-stage)

temperature measurement

overheating protection (safety thermostat)

function indication lamps

room thermostat connection

TECHNICAL DATA
Type Power Temp. max. Pressure max. Back pressure Fire chamber dimensions Water contents Pressure drop Efficiency Weight
kW bar mbar mm lit mbar ∆T=20K % kg
ENP 35 35 90 6 0,2...0,4 320x400 55 2 91,5 165
ENP 70 70 90 6 0,4...0,6 320x600 75 3 91,5 195
ENP 90 90 90 6 0,4...0,6 320x750 95 5 91,5 220
ENP 120 120 90 6 0,6...1,0 370x700 139 6 91,5 220
ENP 140 140 90 6 0,6...1,0 370x850 165 7 91,5 290
ENP 180 180 90 6 0,6...1,0 370x1050 200 9 91,5 330
ENP 230 230 90 6 1,0...2,0 450x1000 197 12 93 510
ENP 300 300 90 6 1,0...2,0 450x1240 240 15 93 575
ENP 350 350 90 6 1,0...2,0 450x1430 270 18 93 635
ENP 420 420 90 6 1,0...2,0 450x1000 197 12 93 945
ENP 500 500 90 6 1,0...2,0 610x1250 640 22 93 1.100
ENP 600 600 90 6 1,0...2,0 610x1500 740 22 93 1.120
ENP 700 700 90 6 1,0...2,0 610x1700 820 25 93 1.205
ENP 800 800 90 6 3,0...4,0 735x1490 960 35 93 1.650
ENP 900 900 90 6 3,0...4,0 735x1690 1.060 35 93 1.845
ENP 1000 1.000 90 6 3,0...4,0 735x1840 1.130 40 93 1.845
ENP 1300 1.300 90 6 3,0...4,0 835x1950 1.890 40 93 2.580
ENP 1500 1.500 90 6 3,0...4,0 835x2200 2.070 40 93 2.780
ENP 1800 1.800 90 6 3,0...4,0 835x2500 2.290 40 93 2.980
ENP 2000 2.000 90 6 3,0...4,0 835x2650 2.400 45 93 3.090
DOWNLOAD DOCUMENTS & USEFUL INFORMATION